New Zealand has decided it wants to be a data centre destination. AWS opened its Auckland region in September 2025. Auckland alone now has around 155 MW of live data centre capacity, close to 90 MW under construction and more than 300 MW planned, according to BMI's July 2026 market overview. In Southland, Datagrid is targeting 2028 for the first phase of a hyperscale AI campus. The conversation around these projects centres on power, water, fibre and data sovereignty. Lightning rarely comes up. That is a mistake, and potentially an expensive one.

Low perception, real exposure

New Zealanders tend to think of lightning as something that happens elsewhere. Next to Queensland or Singapore our thunderstorm activity looks modest, and that perception finds its way into design briefs. Too often I see lightning protection treated as a compliance line item: air terminals on the roof, signed off and forgotten.

The trouble is that a data centre does not fail the way a church steeple or a farm shed fails. The building itself is rarely the casualty. What fails is the electronics, the power chain and the plant that keeps everything cool, and those failures are frequently caused by strikes that never touch the building at all.

Two lessons from the hyperscalers

In August 2015, four successive lightning strikes hit the local utility grid serving Google's St Ghislain data centre in Belgium. The building was not struck. The resulting power disturbance briefly dropped storage systems in one of Google's European cloud zones, and a small fraction of customer data was permanently lost. Google accepted full responsibility for the outage.

In September 2018, storms brought lightning-driven voltage sags and swells to Microsoft's South Central US region in Texas. The site transferred to generator power, but the surges took out mechanical cooling systems despite surge suppression being in place. Temperatures climbed and automated shutdowns followed. Services well outside the region were affected through dependencies, and full recovery took around three days.

Neither operator is careless. The common thread is that the lightning energy arrived through the services rather than the roof, and found the parts of the system that had been treated as someone else's problem.

Where the risk actually sits

A modern data centre is a dense web of conductive paths: HV and LV supply, generator interconnections, copper telecoms, chiller and cooling tower controls, building management systems, security systems and rooftop plant. Each one is a route for surge current into the facility. A strike to an overhead line, or to the ground nearby, can push damaging voltages well inside a building that was never hit.

This is why the IEC 62305 series treats protection as a system rather than a product. Part 3 covers the external system that intercepts a direct strike. Part 4 covers the electrical and electronic systems inside the structure: lightning protection zones, coordinated surge protection, equipotential bonding, shielding and cable routing. For a data centre, Part 4 is where most of the value lies, and in my experience it is where most of the shortcuts are taken.

The gaps I see are predictable. Surge protection is fitted at the main switchboard but not coordinated downstream. Mechanical plant and its controls are left out of the surge design entirely. Telecoms entry points are poorly bonded. Lightning earthing and HV earthing are designed by different parties, with nobody checking that the two work together. In New Zealand, HV earthing at a site intake must be designed to NZECP 35:1993, and the lightning earthing needs to be integrated with it from the start, not added afterwards.

The 2024 standard raises the bar

IEC 62305-2, the international standard for lightning risk assessment, moved to Edition 3 in 2024. The new edition compares a single risk value against a tolerable limit and adds a parallel test on the expected frequency of damage to internal electrical and electronic systems. For data centres that second test matters. A facility can carry a low risk of fire or structural damage and still face an unacceptable frequency of equipment failure. Edition 3 makes that visible, where older assessments often buried it.

The input data matters as much as the method. Edition 3 works from ground strike-point density derived from lightning location system data, under IEC 62858, rather than rough estimates based on thunderstorm days. In a country with as much local variation in storm activity as New Zealand, a regional average is a poor substitute for data specific to the site.

Seeing the storm coming

Protection is only half the picture. Thunderstorm warning systems, covered by IEC 62793, give advance notice of approaching lightning activity. That lets a site move to generator supply on its own terms, defer switching and maintenance work, and clear staff from rooftops and yards before the risk peaks. Deciding when to transfer, rather than letting the storm decide, is a very different operating position.

Three questions worth asking now

Anyone developing, financing or leasing data centre capacity here should put three questions to the design team. Has a risk assessment been carried out to IEC 62305-2:2024 using site-specific strike data, and does it address the frequency of damage to internal systems? Does the surge protection design cover every service entry, including mechanical plant, controls and telecoms, and not just the main switchboard? And have the lightning and HV earthing systems been designed and tested as one system?

New Zealand's pitch to global investors rests on reliability as much as on renewable power. Hyperscale tenants will not accept a lightning outage as an act of nature, any more than Google did. Getting lightning protection right at design stage costs little relative to the value of the build. Getting it wrong is measured in downtime, lost data and damaged reputations.